Product
Low Voltage Fuse
Position: Product   >  Electrical Components >  Low Voltage Fuse

Wholly-scope High-voltage limit-current fuse for protection

Product Introduction :

This product can be used in indoor system of 50Hz and rated voltage 12KV.lt can break any problem current between the fuse melting current and the rated break current.it has the current limit fuse merit of good break;it has also the non-current limit fuse of small current protection.An overall break protection can be achieved.


Type :

Basic parameters :
Rated voltage(KV)

Rated current of the fuse(A)

Rated current of the fuse limit(A)
Rated break current kA
12,24,36
63
10,16,20,25,31.5,40,50,63
63
Selecting principles :
Initialvoltage of the transformer 12KV
Transformer capacity KVA
Ruse Rated current (A)
Fuse type
<125
10
XRNT3A-12 FFLAJ
160
16
200-250
20
315
25
400
31.5
500
40
630
50
800
63

Lnstallation Dimensios:
Wholly-scope' High-voltage limit-current fuse for protection
Wholly-scope' High-voltage limit-current fuse for protection
Technique Data                 
Type
Un(KV)In(A)D(mm)International feference model
XRNT
121076FFLAj
16
20
31.5
40
50
63
8088 
100
Property Cure Diagram :
Wholly-scope' High-voltage limit-current fuse for protection
Wholly-scope' High-voltage limit-current fuse for protection