Product
Circuit Breaker & Automati…
Position: Product   >  Electrical Components >  Circuit Breaker & Automatic Transfer Switch

GV Motor Protection Circuit Breaker

1.Application

GV series motor protection circuit breaker are mainly used fo the overload and short circuit protection of the motor in AC 50/60Hz, up to 660V, 0.1-80A power circuit, as a full-voltage starter to start and cut off the motor, under the AC3 load or for the overload and short circuit protection of the circuit and power equipment in the power distribution network.

2.Specification

TypeStandard power ratings of 3-phase motors 50/60Hz in category AC-3Current setting range (A)
220V380V415V440V500V660V
kWkWkWkWkWkW
GV1-M01------0.1-0.16
GV1-M02------0.16-0.25
GV1-M03------0.25-04
GV1-M04-----0.370.4-0.63
GV1-M05---0.370.370.550.63-1
GV1-M06-0.37-0.550.751.11-1.6
GV1-M070.370.751.11.11.11.51.6-2.5
GV1-M080.751.51.51.52.232.5-4
GV1-M101.12.22.233.744-6
GV1-M142.24445.57.56-10
GV1-M2047.57.57.5101110-16
GV1-M215.51099111516-20
GV1-M225.51111111518.520-25
GV2-M327.515151518.52624-32
GV3-M255.51111111518.516-25
GV3-M401118.52222253325-40
GV3-M6315303333405540-63
GV3-M8022404545556356-80